Chapter 3 - A New Method for an Improved Evaluation of Voltage Dips in Presence of VT Saturation Effects

Chapter 3 - A New Method for an Improved Evaluation of Voltage Dips in Presence of VT Saturation Effects

Articolo

Book on Power Quality - Cambridge Scholars Publishing, vol. 549, pp. 55-59, Maggio -2014.

Richiedi il materiale

R. Chiumeo (RSE SpA) , C. Gandolfi (RSE SpA) , L. Garbero (RSE SpA) , L. Tenti (RSE SpA), Enrico Carpaneto (Politecnico di Torino)

EFFICIENZA 2014 - Risparmio di energia elettrica nei settori: civile industria e servizi

La rilevazione dei falsi buchi di tensione nelle reti di media tensione, dovuti a fenomeni di saturazione dei trasformatori di misura durante alcuni eventi (es. un guasto monofase a terra) nelle reti gestite a neutro isolato, richiede l’implementazione di un criterio per il loro riconoscimento. Il criterio si basa sull’analisi della seconda armonica delle tensioni misurate ed è stato implementato nel sistema di monitoraggio sperimentale QuEEN per valutarne l’efficacia. La sua applicazione permette di trattare allo stesso modo le reti gestite a neutro isolato e compensato (esenti dal problema). Il criterio sarà implementato nel sistema di monitoraggio nazionale realizzato dai distributori che interesserà le sbarre di media tensione di tutte le cabine primarie italiane, in conformità con le recenti disposizioni dell'Autorità.

Saturation effects, essentially on network operated with isolated neutral, can give origin to “false” voltage dips, which can affect the on-line voltage monitoring during a few specific events (i.e. single line-to-ground faults). The “false dip” problem, on the other hand, can be considered negligible in compensated neutral networks. A new criterion has been developed, based on the detection of a second harmonic component in the measured voltages, which, once provided with the proper setting parameters, can succeed in identifying “false” dips.

The criterion effectiveness has been evaluated on field, on the data acquired by the Italian power quality experimental monitoring system QuEEN. The major advantage of the filter implementation in the monitoring system is that, from now on, network operated with isolated neutral could be considered quite similar to those operated with neutral compensation from the point of view of voltage dip performance. The method is to be implemented in the national monitoring system about to be developed by the DSO’s which will concern the monitoring of the MV busbars of all the Italian primary substations, in accordance with the recent disposals of the Italian Regulator.