Diagnostic techniques of MV cable joints under different environmental conditions

Publications - Paper

Diagnostic techniques of MV cable joints under different environmental conditions

The article reports the results and the advances of the experimentation in progress at the RSE laboratories for a diagnostic analysis of the causes of failures that affect MV cable joints, especially during the summer periods.

The article reports the results and the advances of the experimentation in progress at the RSE laboratories for a diagnostic analysis of the causes of failures that affect MV cable joints, especially during the summer periods.

 

To this purpose two different ad hoc experimental set-ups, consisting of cables equipped with different types of joints to form a ring in short-circuit, have been realized. The rings, energized at rated voltage, are loaded with current to reproduce the daily load variation typical of a MV cable network.

 

The first set-up simulated the reduced thermal conductivity of the soil during summer periods and the second, now under test, allows to simulate, in a controlled way, the presence of rain, even of considerable intensity.